FM approved X-purge control system for Division 1 environments. X-purge designed for use on customer supplied enclosure.
Division 1, X-Purge Control, Stand-Alone
Unit of Measure

Standard Features and Benefits

Ratings

N/A Division 1

Materials

Purge Control Main Panel, Interface Box and All Mounting Screws

N/A 304 Stainless Steel #4 Finish

Input/Output (I/O) Casting and Lid

N/A Cast Aluminum

Input/Output (I/O) Casting Bolts

N/A Irradiated Steel

Physical Dimension

Dimensional Drawing

N/A Dimensional Drawing

Outer Box Height

N/A 17.50 in

Outer Box Width

N/A 11.50 in

Outer Box Depth

N/A 10.81 in

Inside Depth

N/A 4.00 in

Outside Depth

N/A 5.63 in

Outer Box Weight

N/A 25 lb

Interface Box Height

N/A 17.50 in

Interface Box Width

N/A 11.50 in

Interface Box Depth

N/A 5.00 in

Interface Box Weight

N/A 5 lb

Environmental

Non-Condensing Relative Humidity

N/A 10 to 95 %

Operating Temperature

N/A 0 to 50 ºC32 to 122 ºF

Storage Temperature

N/A 0 to 70 ºC32 to 158 ºF

Electrical

Maximum Power Usage

N/A 5 W

Maximum Switching Current Capacity

N/A 5 A10 A

Maximum Switching Voltage Capacity for 5 Ampere (A) Current

N/A 120 V

Maximum Switching Voltage Capacity for 10 Ampere (A) Current

N/A 240 V

Note for Electrical

N/A FCC Class A computing device

Pressure and Air Requirements

Incoming Air Pressure (Customer Air Input)

N/A 20 to 60 psi

Operating Pressure

N/A 1 to 4 inWc

Air Flow During Purge

N/A 40 to 300 scfh

Controls Monitoring

Controls Monitoring

N/A
  • Air Connection Kit
  • Conduit Seal Kit
  • I.S. Keyboards and Pointing Devices
  • Video/Keyboard/Pointing Device Extender Systems

Options

Accessories

N/A 9026 - Conduit Seal Kit 9047 - Air Connection Kit

Additional Information

Additional Information

N/A Class I & II, Division 1, Group C-G FM Approved Purge Control (X-Purge), Stand-Alone, Includes Interface Box.